Grid capacity

The connection capacity grid operators publish for a substation, and the stations upstream of it.

The Headroom tab

Where a grid operator publishes how much connection capacity is left at a substation, its page carries a Headroom tab with the figures as the operator states them: what is available, used and committed, the requests in the connection queue, and the split by transformer or voltage level when the operator gives one. When a figure covers a group of substations, the tab says so and names the group. The publisher and the date of its figures are shown under them.

Operators publish in different ways, so what the tab holds varies from one operator to the next. On the Assets list, Has grid capacity keeps only the substations that carry such figures. These are the operator's published figures, not a connection offer: a connection request or study is the firm answer.

Upstream substations

On a substation's page, under its specifications, Upstream substations lists the stations above this one, each linked to its own page: its Parent station, its Transmission source, or a station that Feeds this station, as the operator names them. Hover a card to see who published the link.

Feeding station

Many distribution operators publish capacity only at their HV/MV substations, and do not say which of them feeds each smaller substation. Where such an operator publishes its medium-voltage network, we trace the link ourselves: we follow the lines from each HV/MV substation to the substations they reach, and name the closest along the lines as its Feeding station, with the length of line between them and the capacity left there.

  • When the next candidate is 5 km or more further along the lines, one station is named. Checked against substations that only one station could reach, that answer was right 99 times in 100.
  • When it is 1 to 5 km further, both are named, each as One of two feeding stations, because either may feed it.
  • When it is closer than that, nothing is shown.

Operators switch feeders between stations, so this is the normal configuration, not a guarantee. The trace is redone each time the operator republishes its network.